M10 (20Nm)
Generator Voltage Transformer

UGER D25

The UGER D25 is used for measurement and protection in applications with vibration requirements like power generators. The single pole indoor voltage transformer can be used up to 17,5kV.

2/√3kV -15/√3kV
100/√3V or 110/√3V, other options available on request
As required. For example 10, 15 or 30VA
Ask an offer now
We never go for the simplest solution, but for the best solution, for you, as a customer. Please contact me for the best solution for you.
Wim van Turennout, Key Account Manager
+31 (0)6 2039 5494
Order specifications

For the customized design of your ELEQ voltage transformer the following information is required:

Mandatory
Rated primary voltage
Rated secondary voltage
Rated output
Accuracy class
Frequency

Optional
Transformer requirement with separated windings
Other relevant requirements

General Technical Specifications
This product is designed to be safe under the following conditions:
Environmental conditions
Indoor use
-25°C .. +80°C, other temperatures on request
5% .. 95%, non condensing
Max. 1000m above NN; at >1000m data required
IP20
Application conditions
IEC 61869-3 / IEEE C57.13, etc.
500VA measuring winding 100VA residual winding
1,9 x Un for 8 h, 1,2 x Un continuous
17,5/38/75kV
50/60Hz
E
M10 (20Nm)
Screw terminals M5 (max. 2,5Nm)
As required. For example 0,2, 3P
Downloads
The following downloads are available for this product.